# Snarfnet Homelab Power Resilience & UPS Automation Plan
This document details the power resilience strategy, tiered graceful shutdown sequence, and integration architecture for the **snarfnet** homelab centered around the primary **NUT (Network UPS Tools) Master Server**.
---
## 1. Core Architecture & IP Assignments
The power resilience architecture uses a centralized **NUT Master Server** host that polls connected UPS hardware and broadcasts status alerts (`ONBATT`, `LOWBATT`, `ONLINE`, `FSD`) across all homelab VLANs.
| Role | Hostname / Identifier | Target IP | Subnet / VLAN | Description |
|---|---|---|---|---|
| **NUT Master Server** | `nutserver.snarfnet.net` | `14.4.4.44` | VLAN 50 (Smart Home) | Primary NUT `upsd` daemon polling physical UPS via USB/Serial/SNMP. |
| **NUT Web Dashboard** | `peanut.snarfnet.net` | `140.44.4.70:8050` | VLAN 20 (Compute / Swarm) | Peanut container UI consuming `14.4.4.44:3493`. |
| **Smart Home Automation** | `homeassistant.snarfnet.net` | `14.4.4.20` | VLAN 50 (Smart Home) | Home Assistant integration monitoring `14.4.4.44:3493` for alerts/triggers. |
| **Centralized Monitoring** | `zabbix.snarfnet.net` | `140.44.4.61` | VLAN 20 (Spaceport K3s) | Zabbix Agent 2 / NUT exporter polling `14.4.4.44:3493`. |
| **Primary Storage 1** | `sn-nas.snarfnet.net` | `14.10.10.71` | VLAN 40 (Storage) | Synology DSM UPS client polling `14.4.4.44`. |
| **Primary Storage 2** | `snarfnas.snarfnet.net` | `14.10.10.72` | VLAN 40 (Storage) | Synology DSM UPS client polling `14.4.4.44`. |
---
## 2. Power Resilience Topology Map
```mermaid
flowchart TD
subgraph Grid ["Utility Power Grid"]
Mains["Main AC Power Supply"]
end
subgraph PowerHardware ["Power Protection"]
UPS["Central UPS Hardware"]
end
subgraph NUTMasterHost ["NUT Master Node (14.4.4.44)"]
UPSD["upsd Daemon (Port 3493)"]
UPSMON_M["upsmon (Master)"]
end
subgraph Dashboards ["Monitoring & Alerting"]
Peanut["Peanut Dashboard\n(peanut.snarfnet.net:8050)"]
HA["Home Assistant\n(14.4.4.20)"]
Zabbix["Zabbix Server\n(140.44.4.61)"]
end
subgraph Slaves ["UPS Slaves (upsmon Client Nodes)"]
Harvester["Spacedock HCI Nodes\n(140.44.4.81 - 83)"]
K3sControl["K3s Control Planes\n(Aerodrome & Spaceport)"]
K3sWorkers["K3s Worker Nodes"]
Swarm["Shipyard Swarm Nodes\n(140.44.4.71 - 75)"]
NAS["Synology NAS Arrays\n(14.10.10.71 / 72)"]
end
Mains --> UPS
UPS -- USB / SNMP --> UPSD
UPSD --> UPSMON_M
UPSD -- TCP 3493 --> Peanut
UPSD -- TCP 3493 --> HA
UPSD -- TCP 3493 --> Zabbix
UPSD -- TCP 3493 (Slave Broadcast) --> Harvester
UPSD -- TCP 3493 (Slave Broadcast) --> K3sControl
UPSD -- TCP 3493 (Slave Broadcast) --> K3sWorkers
UPSD -- TCP 3493 (Slave Broadcast) --> Swarm
UPSD -- TCP 3493 (Slave Broadcast) --> NAS
```
---
## 3. Tiered Shutdown Hierarchy & Execution Timeline
To prevent data corruption and unexpected hard cutoffs, hosts shutdown in staged tiers based on power outage duration and battery level.
```
+-------------------------------------------------------------------------+
| [T+0s] Grid Power Outage -> NUT Master (14.4.4.44) detects ONBATT |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| [T+3m / Batt <= 80%] TIER 1: Non-essential Workloads |
| - Dev VMs, transcoders, test containers in Swarm & K3s drained |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| [T+7m / Batt <= 50%] TIER 2: Hypervisors, Compute Workers & Storage |
| - Harvester spacedock VMs gracefully shut down via virsh/API |
| - Aerodrome & Spaceport worker nodes gracefully halt |
| - Synology NAS arrays (14.10.10.71/72) enter Safe Mode & unmount pools |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| [T+12m / Batt <= 30%] TIER 3: Control Planes & Management Stack |
| - Aerodrome (140.44.4.11-13) & Spaceport (140.44.4.41-44) Control Planes|
| - Swarm Manager (140.44.4.71) & AI Nodes (140.44.4.7-8) halt |
+-------------------------------------------------------------------------+
|
v
+-------------------------------------------------------------------------+
| [T+15m / Batt Low] TIER 4: Forced Shutdown (FSD) & Hardware Cutoff |
| - NUT Master (14.4.4.44) issues FSD signal to remaining clients |
| - NUT Master issues `upsdrvctl shutdown` (cuts UPS load outlet) |
| - Network Core (UDM Pro 14.44.4.1) stays alive until final battery drop |
+-------------------------------------------------------------------------+
```
---
## 4. Configuration Blueprint & Service Integrations
### A. NUT Master Server (`14.4.4.44`) Configuration Files
#### `/etc/nut/ups.conf`
```ini
[snarf-ups]
driver = usbhid-ups
port = auto
desc = "Snarfnet Main Server Rack UPS"
pollinterval = 5
```
#### `/etc/nut/upsd.conf`
```ini
LISTEN 14.4.4.44 3493
LISTEN 127.0.0.1 3493
MAXAGE 15
```
#### `/etc/nut/upsd.users`
```ini
[admin]
password = SUPER_SECRET_ADMIN_PASS
actions = SET
instcmds = ALL
[upsmon_master]
password = MASTER_MONITOR_PASS
upsmon master
[upsmon_slave]
password = SLAVE_MONITOR_PASS
upsmon slave
[peanut]
password = PEANUT_MONITOR_PASS
upsmon slave
```
#### `/etc/nut/upsmon.conf`
```ini
MONITOR snarf-ups@14.4.4.44 1 upsmon_master MASTER_MONITOR_PASS master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /usr/local/bin/nut-notify.sh
POWERDOWNFLAG /etc/killpower
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
NOTIFYFLAG FSD SYSLOG+WALL+EXEC
NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC
NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC
```
---
### B. Client Node Configuration (`upsmon` Slave)
Applies to Harvester hypervisors, K3s master/worker hosts, Docker Swarm hosts, and Debian Linux nodes.
#### `/etc/nut/upsmon.conf` (Slave Mode)
```ini
MONITOR snarf-ups@14.4.4.44 1 upsmon_slave SLAVE_MONITOR_PASS slave
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POWERDOWNFLAG /etc/killpower
HOSTSYNC 15
DEADTIME 15
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
```
---
### C. Synology NAS Integration (`14.10.10.71` & `14.10.10.72`)
1. Log into **DSM Console** $\rightarrow$ **Control Panel** $\rightarrow$ **Hardware & Power** $\rightarrow$ **UPS**.
2. Check **Enable UPS Support**.
3. Select UPS Type: **Synology UPS Server / Network NUT Server**.
4. Network UPS server IP address: **`14.4.4.44`**.
5. Set **Time before Synology NAS enters Standby Mode**: `Customize time` $\rightarrow$ `5 minutes` (or `Upon low battery`).
---
### D. Peanut Web Dashboard (`peanut.snarfnet.net`)
Peanut runs on Docker Swarm (`140.44.4.70:8050`). Ensure the Peanut service configuration references the NUT server at `14.4.4.44`:
#### Updated `docker-deployments/peanut.yml`
```yaml
services:
peanut:
image: brandawg93/peanut:latest
ports:
- "8050:8050"
environment:
- TZ=America/New_York
- NUT_HOST=14.4.4.44
- NUT_PORT=3493
- NUT_USER=peanut
- NUT_PASSWORD=PEANUT_MONITOR_PASS
volumes:
- peanut_config:/config
volumes:
peanut_config:
driver: local
driver_opts:
type: none
o: bind
device: /mnt/swarm_shared/legacy_volumes/peanut/
```
---
### E. Home Assistant (`14.4.4.20`) Integration & Automation
1. Navigate to **Settings** $\rightarrow$ **Devices & Services** $\rightarrow$ **Add Integration** $\rightarrow$ **Network UPS Tools (NUT)**.
2. Host: **`14.4.4.44`**, Port: **`3493`**.
3. Username: **`upsmon_slave`**, Password: **`SLAVE_MONITOR_PASS`**.
#### Automation Snippet (`automations.yaml`)
```yaml
alias: "Power Resilience: Grid Power Lost Alert"
trigger:
- platform: state
entity_id: sensor.snarf_ups_status
to: "On Battery"
action:
- service: notify.gotify
data:
title: "⚡ Power Outage Alert"
message: "Grid power failure detected! Homelab is running on UPS battery (14.4.4.44). Tiered shutdown in progress."
priority: 8
```
---
## 5. Power Restoration & Auto-Boot Sequence
When grid power returns, systems auto-recover in reverse order:
1. **UPS AC Mains Restored**: Physical UPS re-enables output outlets once battery reaches safe threshold ($\ge 20\%$).
2. **Phase 1 - Gateway & Edge**: UDM Pro (`14.44.4.1`) & Core switches boot up and establish internal VLAN routes.
3. **Phase 2 - NUT Master**: Host at `14.4.4.44` boots (BIOS `Restore AC Power` set to `Always On`). `upsd` service starts.
4. **Phase 3 - Storage NAS**: Synology NAS nodes (`14.10.10.71`, `14.10.10.72`) auto-boot upon power recovery.
5. **Phase 4 - Control Planes & Hypervisors**:
- Harvester `spacedock` hosts (`140.44.4.81-83`) boot via Wake-on-LAN / IPMI / BIOS settings.
- K3s master nodes (`aerodrome` & `spaceport`) boot, resume etcd quorum.
6. **Phase 5 - Worker Compute & Workloads**: Worker nodes boot; Kubernetes and Docker Swarm automatically reschedule workloads.